    4 MW - NEW GENERATING SETS

    4 MW - NEW GENERATING SETS

    Jumlah Pesanan:
    Negara Asal:
    Inggris

    Keterangan :

    OFFER FOR BRAND NEW 4MW 1000RPM 11KV COMBINED BASE PLATE AVM MOUNTED CONTINUOUS LOAD GENERATORS.

    Generator Specification and Scope of Supply

    One 16RK270 Diesel Engine

    The engine supplied would be modified from standard to accommodate for MFO and Biodiesel operation if required including

    ⢠Water Cooled Exhaust Valve Seats ( IMPS Design Cylinder Heads)
    ⢠Fitting of Exhaust Valve Rotators ( IMPS Design)
    ⢠Water Cooled Injector Nozzles
    ⢠Two Piece Piston Assemblies with Steel Crown and Forged Aluminium Skirt

    Additional modifications undertaken by us would be

    ⢠IMPS Modified Connecting Rod
    ⢠IMPS Modified Bearings
    ⢠IMPS Modified Lubricating Oil Pumps
    ⢠Single Turbocharger arrangement instead of double

    Coupled to Leroy Somer Alternator

    Continuous Rating 5000 KVA / 4000 KW 11KV 750 RPM

    THE GENERATOR OFFERED WILL BE MOUNTED ON A COMBINED BASEPLATE COMPLETE WITH ANTI VIBRATION MOUNTS

    
    List of items included

    Engine Cooling System Per Engine

    § Engine Mounted Primary and Secondary Water Pumps
    § Appropriate gauges and monitoring equipment
    § Secondary Water Radiator
    § Jacket and Lub Oil Heat Exhangers

    Engine Starting System

    § Diesel driven air compressor x 1
    § Motor driven air compressor x 1
    § Air receiver x 1
    § Starting air system ( mounted on engines)
    § Appropriate gauges and monitoring equipment

    Engine Charge Air System x 1

    § Manifolding
    § Turbine and Charge Air Cooler ( mounted on engines)
    § Appropriate gauges and monitoring equipment
    § Oil Bath Air Filter

    Engine Exhaust System x 1

    § Residential exhaust silencer
    § Expansion bellows
    § Uptakes and manifolding
    § Appropriate gauges and monitoring equipment

    Engine Lubricating Oil System x 1

    § Motorised Lub Oil Priming Pump
    § Engine Mounted Lub Oil Pumps ( x2)
    § Appropriate gauges and monitoring equipment
    § Lubricating Oil Filtration Equipment

    Fuel Oil System x 1

    § Engine Driven fuel oil pressurising pump
    § Appropriate gauges and monitoring equipment
    § Filtration Equipment

    Instrumentation For The Installation Is Supplied In Accordance With The Information Given Below

    Parameter Mounted Gauges Local Control Panel
    Secondary Water Pump Inlet Pressure
    Secondary Water Pump Outlet Pressure
    Secondary Water Intercooler Inlet Temperature
    Secondary Water Intercooler Outlet Temperature 
    
    
     
    
    
    
    Lube Oil Engine Outlet Pressure
    Lube Oil Engine Inlet Pressure
    Lube Oil Inlet Temperature To Engine
    Lube Oil Outlet Temperature From Engine
    Lube Oil Piston Return Temperature ( For Large End Bearing Monitoring)
    Lube Oil Main Bearing Temperature 
    
    
    

    
    
    
    
    
    
    Jacket Water Engine Inlet Temperature
    Jacket Water Engine Outlet Temperature
    Jacket Water Engine Inlet Pressure
    Jacket Water Engine Outlet Pressure 
    
    
     
    
    
    
    Charge Air Cooler Air Inlet Temperature
    Charge Air Cooler Air Outlet Temperature
    Charge Air Manifold Temperature
    Charge Air Manifold Pressure 
    
    
     
    
    
    
    Exhaust Gas Temperature Cylinder 1
    Exhaust Gas Temperature Cylinder 2
    Exhaust Gas Temperature Cylinder 3
    Exhaust Gas Temperature Cylinder 4
    Exhaust Gas Temperature Cylinder 5
    Exhaust Gas Temperature Cylinder 6
    Exhaust Gas Temperature Cylinder 7
    Exhaust Gas Temperature Cylinder 8
    Exhaust Gas Temperature Cylinder 9
    Exhaust Gas Temperature Cylinder 10
    Exhaust Gas Temperature Cylinder 11
    Exhaust Gas Temperature Cylinder 12
    Exhaust Gas Temperature Cylinder 13
    Exhaust Gas Temperature Cylinder 14
    Exhaust Gas Temperature Cylinder 15
    Exhaust Gas Temperature Cylinder 16
    Exhaust Gas Inlet Temperature to Turbocharger
    Exhaust Gas Outlet Temperature from Turbocharger

    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    Alternator Pedestal Bearing Temperature
    Alternator Pedestal Bearing Pressure
    Alternator Stator Winding Temperatures 

    
    
    
    Engine RPM  
    Turbocharger RPM  

    ALL OF THE ABOVE MEASUREMENTS WILL BE CONFIGURED IN THE LOCAL CONTROL PANEL PLC FOR ALARM AND SHUTDOWN AT PRECONFIGURED PARAMETERS

    Vibration Monitoring System

    A Vibration Monitoring System will be fitted to the generator and configured to the protection panel for emergency shutdown in the event of out of parameter vibration

    Bearing Temperature Monitoring System

    A Main and Large End Bearing Monitoring System will be fitted to detect early signs of any bearing failure. This will be configured to the panel for emergency shutdown in the event of excessive temperatures being recorded.

    Mechanical Protection & Associated Systems

    Overspeed governor operates the pneumatic trip valve, which releases the fuel-purge system.
    Lubricating oil pressure low, or loss of control air pressure.
    ( Pressure trip operates pneumatic trip valve. Racks move to â zero fuelâ position.)
    Alternator is protected by a microswitch operated by the fuel pump control shafts.

    Selector Switch Auto Start Module For Local/ Remote Start.

    Engine start push button.
    Engine stop push button.
    Emergency stop button

    ADDITIONAL MONITORING OR PROTECTION CAN BE SUPPLIED IN ACCORDANCE WITH CUSTOMERS REQUIREMENTS

    Engine Control Panel & Automatic Synchronising Control Panel Package

    § Engine / generator control micro processor type with engine control circuits & protections, synchronising & load share / demand & control function plus LCD screen to display engine alarms status ( to be assigned) etc.
    § Control push buttons for mode selection manual / off / auto
    § LCD screen display of electrical metering functions
    o AC measurements
    o Voltage per phase
    o Current per phase
    o Frequency
    o Kilowatt
    o KVA
    o RPM
    o Battery voltage
    § Protection Included
    o Reverse power
    o Under & over voltage
    o Under & over frequency
    o Overspeed
    § Emergency stop push button
    § Battery charger ammeter & voltmeter
    § Battery charger on / off switch
    § Mains operated battery charger
    § Set of interposing relays & time delays to suit
    § Set of control circuit fuses to suit
    § Set of control circuit terminals to suit
    § 2nd LCD Screen display of mechanical parameters

    11KV Switchgear Specification

    § Application Generator Incomer Feeder Transformer
    § Configuration Extensible
    § Isolatable Pattern Vertical Isolation, Horizontal Draw Out
    § Insulation Medium Vacuum
    § Location Indoor
    § System Voltage 11, 000 Volts
    § Current Rating of OCB To Be Confirmed
    § Current Rating of Busbars To Be Confirmed
    § Frequency 50 Hertz
    § Protection & Metering Electronic Overcurrent & Earth Fault, Centre Tapped
    Ammeter, Kilovolt Meter, Kwh Meter
    § Tripping Supply 30 VDC
    § Incoming Cable Entry Dry Type Box Suitable for Cable from Below
    § Outgoing Cable Entry Dry Type Box Suitable for Cable from Below

    Transformers

    1 x 11KV / 480 â 277 V LV Station Transformer ( Rating TBA)
    1 x 11KV / System Voltage

    Neutral Earth Resistor ( Rating TBA)